Series 24 Specifications
BURNER
HEATING
WATER
BOILER WEIGHT
NET I=B=R RATING
INPUT
SURFACE
NET
PRESSURE
CONTENT
w/ WATER
GROSS
(SQ. FT.)
FIREBOX
IN
(GAL.)
(LBS.)
VENT
BOILER
HORSE- OUTPUT
SQ. FT.
MBH
MBH
OIL
GAS
VOLUME FIREBOX
DIA.
MODEL
POWER
(MBH)
STEAM
STEAM
WATER
(GPH)
(MBH)
STEAM
WATER
(CU. FT.) (“W.C.”)
STEAM
WATER
STEAM
WATER
(IN.)
24-03
10.2
342
1071
257
297
3.05
438
34.2
37.0
3.2
.33
44.5
66.0
1439
1618
7
24-04
14.1
471
1471
353
410
4.10
594
48.6
54.3
4.8
.38
53.0
75.0
1811
1995
7
24-05
18.9
634
1983
476
551
5.50
792
63.0
71.5
6.4
.31
61.5
84.0
2184
2372
8
24-06
23.8
797
2492
598
693
6.90
990
77.5
88.8
7.9
.38
70.0
93.0
2557
2749
8
24-07
28.0
937
2929
703
815
8.10
1174
91.9
106.0
9.5
.36
78.5
102.0
2930
3126
8
24-08
32.5
1087
3396
815
945
9.40
1358
106.3
123.3
11.0
.35
87.0
111.0
3303
3503
10
24-09
39.3
1316
4146
995
1148
11.40
1641
120.7
140.5
12.6
.35
95.5
120.0
3676
3880
10
24-10
45.0
1505
4788
1149
1309
13.00
1867
135.1
157.8
14.2
.40
104.0
129.0
4048
4257
10
24-11
50.5
1690
5429
1303
1470
14.60
2093
149.5
175.0
15.7
.45
112.5
138.0
4421
4634
12
24-12
55.3
1852
5983
1436
1610
16.00
2320
164.0
192.3
17.3
.49
121.0
147.0
4794
5011
12
Since 1949, homeowners have depended on us
for quality, value and service.
3633 I Street, P.O. Box 14818
Philadelphia, PA 19134
Phone: (215) 535-8900 Fax: (215) 535-9736
www.crownboiler.com
Commercial Hot Water or Steam Boiler
Commercial Hot Water or Steam Boiler
Beckett Gas Burners
(Natural Gas)
Min. Inlet
Gas
Boiler
Burner
Rate
STD. Motor
Pressure
Train
Model
Model
Control
Voltage
H.P.
(in W.C.)
Size
24-03
CG10.1S
On/Off
120/60/1
1/3
3.2
1”
24-04
CG10.4S
On/Off
120/60/1
1/3
3.6
1”
24-05
CG10.5S
On/Off
120/60/1
1/3
4.3
1-1/4”
24-06
CG10.6S
On/Off
120/60/1
1/3
4.4
1-1/2”
24-07
CG15.3S
Lo/Hi/Lo
120/60/1
1/2
4.0
1-1/2”
24-08
CG15.4S
Lo/Hi/Lo
120/60/1
1/2
4.4
1-1/2”
24-09
CG25.2S
Lo/Hi/Lo
120/60/1
3/4
4.3
1-1/2”
24-10
CG25.3S
Lo/Hi/Lo
120/60/1
3/4
4.9
1-1/2”
24-11
CG25.4S
Lo/Hi/Lo
120/60/1
3/4
4.9
1-1/2”
24-12
CG50.2S
Lo/Hi/Lo
208-240/60/1
2
3.9
1-1/2”
Minimum gas pressures shown are for standard burners only.
See manual for minimum gas pressure when other size gas trains are used.
Beckett Oil Burners
Boiler
Burner
Rate
STD. Motor
Model
Model
Control
Voltage
H.P.
24-03
CF500
On/Off
120/60/1
1/3
24-04
CF800
On/Off
120/60/1
1/3
24-05
CF800
On/Off
120/60/1
1/3
24-06
CF1400
Lo/Hi/Lo
120/60/1
1/2
24-07
CF1400
Lo/Hi/Lo
120/60/1
1/2
24-08
CF1400
Lo/Hi/Lo
120/60/1
1/2
24-09
CF2300A
Lo/Hi/Lo
120/60/1
3/4
24-10
CF2300A
Lo/Hi/Lo
120/60/1
3/4
24-11
CF2500
Lo/Hi/Lo
240/60/1
2
24-12
CF2500
Lo/Hi/Lo
240/60/1
2
S24-12/05 (25M)
PN980521
AVAILABLE FROM
Notes:
1. Trim suffix
S = Steam Boiler
W = Water Boiler
Fuel suffix
N = Natural Gas
O = Oil
2. I=B=R net ratings shown are based on piping and pick-up allowances which vary from 1.333 to 1.289 for steam and 1.15 for water. Consult manufacturer for installations having unusual piping and pick-up
requirements, such as intermittent system operation, extensive piping systems, etc. The I=B=R burner capacity in GPH is based on oil having a heat value of 140,000 BTU per gallon.
3. Firebox volume does not include added volume of 8” extended burner mounting plate (BMP). If 8” BMP is specified (refer to Figure 1), add 0.7 cu. ft. to volume listed above.
4. Boiler ratings are based on 12.5% CO2 (oil) and 9.7% CO2 (natural gas), + .10” (inches) water column pressure at boiler flue outlet. Ratings shown above apply at altitudes up to 1000 feet on oil and 2,000
feet on gas. For altitudes above those indicated, the ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
Maximum Allowable Working Pressure: Steam Boiler – 15 PSI, Water Boiler – 50 PSI
Standard Safety (Relief) Valve Set Pressure: Steam Boiler – 15 PSI, Water Boiler – 30 PSI